GREENWORLD SECTOR-7 // MONITORING // ALARM MATRIX
ALL SYSTEMS NOMINAL ·
Controlled Document · VC-ENG-2400

Alarm & Escalation Matrix

The authoritative register of every monitored alarm condition across the facility — its trigger threshold, severity, automated response, notified roles, escalation timing, and the bound standard operating procedure.

Doc ID: VC-ENG-2400 Rev: H · 2089-11-04 Owner: S. Mbeki, ENG-NOC & Reliability Approver: Dr. H. Voss, Director NOC: ext. 7240 (24/7) Review: Quarterly

1. Severity Model

Five tiers govern response. Auto-responses are executed by CHLORA within its authority; anything above T2 stages for human confirmation. Escalation timers start at acknowledgement-required and trigger the next notify tier if unacked.

TierMeaningDefault Escalate-If-Unacked
INFOLogged deviation, in band
WATCHApproaching threshold30 min
CAUTIONThreshold crossed, recoverable10 min
CRITICALSpecimen / loop at risk3 min
BREACHContainment / safety eventImmediate page

2. Alarm Condition Matrix

ConditionTrigger ThresholdSeverityAuto-ResponseNotified RolesEscalateSOP
Turgor collapse Stem turgor < 300 kPa, falling > 40 kPa/10 min CRITICAL Irrigation loop boost; CWSI re-scan tasked Zone Lead, Duty Mgr, NOC 3 min SOP-CULT-031
Containment pressure loss Vault Δp > −15 Pa (toward positive) for > 5 s BREACH Damper close, scrubber max, interlock lockdown (fail-safe) Incident Cmdr, CBO, NOC Immediate page SOP — Emergency Breach
Toxin VOC spike Headspace VOC > 5 ppm or ethylene > 2 ppm CRITICAL Local exhaust to scrubber; zone access hold Zone Lead, Safety Officer, NOC 3 min SOP-SAFE-018
Hydro-loop overpressure Loop pressure > 2.4 bar, rising CAUTION Relief valve modulate; pump VFD throttle Hydro Eng, NOC 10 min SOP-FAC-022
Hydro-loop underpressure Loop pressure < 1.8 bar for > 60 s CAUTION Cross-feed from backup loop; leak isolation scan Hydro Eng, NOC 10 min SOP-FAC-023
Mesh node offline Missed heartbeat > 90 s WATCH Mesh re-route; FRAM replay on return ENG-NOC 30 min SOP-ENG-009
Zone mesh dark (>0.8%) > 0.8% of a zone's nodes offline CAUTION Bridge-node dispatch ticket; tighten neighbor sampling Sensing Lead, NOC 10 min SOP-ENG-010
GCL-4 motion detected Vault motion sensor active, no scheduled access BREACH Vault lockdown; lights to spectrum-hold; record Incident Cmdr, CBO, Security Immediate page SOP — Emergency Breach
Chlorophyll fluorescence drop Fv/Fm < 0.70 across a cluster CAUTION Targeted canopy re-scan; CHLORA decline forecast Cultivar Tech, NOC 10 min SOP-CULT-027
CWSI water-stress high CWSI > 0.6 sustained 15 min CRITICAL Irrigation cue; fogger engage; VPD trim Zone Lead, NOC 3 min SOP-CULT-031
CO₂ out of band < 380 ppm or > 450 ppm, 10 min WATCH Dosing/ventilation loop correction ENG-NOC 30 min SOP-FAC-015
MDF strand failure Link down; redundant paths < 3 CAUTION Pheromone re-route; bulk traffic pause Platform Eng, NOC 10 min SOP-ENG-012
MDF core loss One core cluster unreachable CRITICAL Active-active failover to surviving core Platform Lead, Duty Mgr, NOC 3 min SOP-ENG-013
CHLORA confidence low Decision score < 0.80 WATCH Auto-demote autonomy to T0 advisory ENG-NOC 30 min SOP-ENG-014
Spoofed/invalid packet Ed25519 signature mismatch CRITICAL Drop packet; quarantine node; security event Security, Platform Eng, NOC 3 min SOP-SEC-004
Power transfer event Mains loss; on backup/generator CRITICAL Load-shed scavenger class; verify core/containment power Power Eng, Duty Mgr, NOC 3 min SOP-FAC-001
Drone fleet availability low < 94% fleet available WATCH Re-task priority zones; bay charge audit Fleet Lead, NOC 30 min SOP-ENG-016
Node battery low Node SoC < 15% WATCH Replacement ticket; reduce sample rate ENG-NOC 30 min SOP-ENG-009

3. Notification & Escalation Logic

GCL-4 standing order. Any BREACH involving a GCL-4 specimen invokes facility lockdown and CBO master override authority per VC-ENG-2300 §5. No autonomous action may escalate beyond lockdown without T3 human confirmation.