Barometric Pressure (zone)
VC-MET-112 — the absolute air pressure of a cultivation zone, the reference baseline for gas-concentration corrections and a leading indicator of containment-seal integrity.
Definition
Barometric Pressure is the absolute air pressure within a cultivation zone, in hectopascals. It is sensed directly by MEMS absolute-pressure transducers on the PhytoSense Mesh, one per zone plus a facility outdoor reference. While it tracks ambient weather, in a pressure-controlled facility it is also actively managed: cultivation cells are held at a small differential to neighbouring spaces, so the zone-to-reference pressure delta is itself a monitored quantity that reveals fan balance and seal condition.
Why it matters
Barometric pressure plays two roles. First, it is the reference baseline that makes other metrics honest: ppm gas readings (CO₂, VC-MET-103) and dissolved-oxygen saturation both depend on absolute pressure, so an uncorrected drift biases the whole gas panel. Second, the zone-to-corridor pressure differential is a containment signal — sustained loss of the intended negative or positive offset means a door is ajar, a fan has failed, or a seal has degraded, which links this metric directly to Containment Integrity (VC-MET-401).
Formula
A directly measured signal. Reported zone pressure is the transducer reading after factory and thermal compensation, with the controlled differential derived alongside:
P_zone = P_raw + c_T(T) + c_cal P_raw MEMS transducer reading (hPa) c_T(T) thermal-compensation term c_cal span/offset from annual barometric reference Containment differential (advisory, links to VC-MET-201): ΔP = P_zone − P_corridor target ΔP held per zone classification (GCL-1..GCL-4); loss of intended ΔP sign or magnitude raises a seal alert. Gas-correction export: k_P = P_zone / 1013.25 → supplied to CO₂ & DO sheets.
Inputs
| Channel | Sensor | Placement | Reference Band | Source |
|---|---|---|---|---|
| P_zone | MEMS absolute barometer (±0.5 hPa) | Cultivation zone, 1× per cell | 995 → 1025 hPa | PhytoSense Mesh |
| P_ref | Outdoor reference barometer | Facility weather station | 980 → 1035 hPa | PhytoSense Mesh |
| P_cor | Corridor barometer | Adjacent corridor (ΔP) | per GCL class | PhytoSense Mesh |
| T | Air temperature | Thermal compensation | VC-MET-100 | PhytoSense Mesh |
Units & Scale
Reported in hectopascals to whole-hPa precision. Pressure is intensive and not summed; the zone figure stands alone, with the zone-to-corridor differential (ΔP, in pascals) reported alongside as the containment-relevant quantity. Confidence degrades to DEGRADED when the zone barometer disagrees with the outdoor reference by more than weather can explain (a drifting transducer) or when the controlled ΔP cannot be held despite a healthy fan command.
Sampling & Source
- Sampled every 1 minute from the PhytoSense Mesh zone, corridor, and outdoor-reference barometers.
- Thermally compensated; the gas-correction factor k_P is exported to the CO₂ and DO sheets.
- Stale handling: a barometer silent > 3 min is dropped; loss of the zone unit falls back to the outdoor reference plus modelled offset with a DEGRADED flag.
- Calibration: annual check against the facility barometric standard; drift > 0.5 hPa raises a metrology work order.
Thresholds
OK
Normal weather-driven range; differential held. No action.
WARN
Deep low (storm) or strong high; verify gas corrections & differential. Review.
CRIT
Extreme weather load or sensor fault; containment-differential at risk. Auto-escalation.
Recent Trend
Zone-A barometric pressure, last 14 sampling roll-ups (hPa):
Interpretation Guidance
| Band | Reading | Likely Driver | Action |
|---|---|---|---|
| 995–1025 hPa | Normal | Ordinary weather; differential held | None; log as reference. |
| 985–994 hPa | Low drift | Approaching low-pressure system | Verify gas corrections; watch ΔP stability. |
| 1026–1035 hPa | High drift | Strong high-pressure system | Verify gas corrections; no plant action. |
| < 985 / > 1035 hPa | WARN | Severe weather or transducer drift | Review; confirm ΔP and CO₂/DO corrections. |
| < 975 / > 1045 hPa | CRIT | Extreme load or sensor fault | Auto-escalation; check containment differential. |
Related Metrics
Atmospheric CO₂
Pressure-corrected from this baseline.
VC-MET-110Dissolved Oxygen
Pressure term in DO saturation.
VC-MET-401Containment Integrity Index
Pressure differential is a seal signal.
VC-MET-100Air Temperature
Thermal compensation input.
VC-MET-111Canopy Airflow Velocity
Fan balance shaping ΔP.
VC-MET-101Relative Humidity
Co-sensed zone air-state.
Related SOPs
- SOP Library — pressure-differential & containment procedures.
- Containment-differential loss response on CRIT — see Containment SOP set in the SOP Library.
- Pressurization-fan interlock & alarm escalation — Monitoring Systems.