GREENWORLD SECTOR-7 // METRICS // VC-MET-306
ALL SYSTEMS NOMINAL ·
METRICS · OPERATIONS & RESOURCE

Hydro-Loop Pressure

VC-MET-306 — the working pressure of the closed hydroponic distribution loop in bar, a two-sided metric guarding against both starvation and over-pressure of the irrigation network.

Metric ID VC-MET-306 Category Operations & Resource Unit bar Type Direct Source PhytoSense Mesh Sampling 30 s Owner Metrology & Telemetry Standards Rev C · Effective 2089-06-01
Current 2.5 bar Nominal 2.2–2.8 bar 30-s cadence Loop transducers via PhytoSense Mesh

Definition

Hydro-Loop Pressure (HLP) is the gauge pressure, in bar, of the closed-loop hydroponic distribution header that feeds nutrient solution to all cultivation benches and spheres. It is read directly from redundant transducers at the loop manifold and is a two-sided control variable: too low and emitters starve, leaving root zones under-irrigated; too high and seals, fittings, and drip lines are stressed toward failure. The nominal band represents the pressure at which every emitter on the loop delivers its rated flow.

Why it matters

The hydro-loop is the facility's circulatory system. A pressure sag can dry a bench within an irrigation cycle and depress turgor and vitality (VC-MET-001) before any soil sensor reacts; an over-pressure event can burst a line and flood a containment cell. Because the failure modes are fast and bidirectional, HLP samples every 30 seconds and carries hard safety interlocks. It is a front-line infrastructure metric on the Operations Dashboard and a direct trigger for pump-control and isolation logic.

Formula

HLP is a directly measured signal; the model below covers transducer voting and calibration:

HLP = median( P_a , P_b , P_c )      [bar, gauge]

where P_a, P_b, P_c are three redundant manifold transducers.
Median voting rejects a single faulted transducer; if two
disagree by > 0.15 bar, the loop flags SENSOR_DISCORD and the
worst outlier is excluded.

Calibration:
  zero offset trimmed against atmospheric reference at each
  maintenance window; span verified at 4.0 bar dead-weight.
  transducer accuracy ± 0.02 bar over 0–6 bar range.

Rate guard (two-sided):
  if |dHLP/dt| > 0.4 bar/min  →  flag PRESSURE_TRANSIENT
     (possible line breach or pump runaway).

No smoothing on the alarm path; a 5-sample median is published
for trend display only.

Inputs

ChannelRoleCadenceReferenceSource
Manifold transducer A/B/CRedundant pressure measurement30 s0–6 bar, ± 0.02PhytoSense Mesh
Pump VFD feedbackPump speed / pressure-control context30 s0–100% dutyPhytoSense Mesh
Atmospheric referenceZero-offset calibrationPer maintenanceBarometricPhytoSense Mesh
Loop flow (downstream)Starvation cross-check30 sL·min⁻¹PhytoSense Mesh

Units & Scale

HLP is reported in bar (gauge) to two decimal places. It is a point measurement at the loop manifold, not an aggregate; sub-loop branch pressures are monitored separately where the distribution tree splits. The published trend uses a 5-sample median for readability, but thresholds act on the unsmoothed voted value. A SENSOR_DISCORD flag is raised when redundant transducers disagree beyond 0.15 bar, degrading confidence until reconciled.

Sampling & Source

Thresholds

Nominal · 2.2–2.8 bar

OK

Every emitter at rated flow. No action.

Warning · < 2.0 / > 3.2 bar

WARN

Low: emitter starvation risk. High: seal stress; trim pump duty.

Critical · < 1.6 / > 3.6 bar

CRIT

Low: line breach / pump loss. High: over-pressure; isolate loop.

Two-sided safety override. HLP alarms on both edges. On the high side, > 3.6 bar trips the pump VFD to minimum and opens the relief bypass within one sample; on the low side, < 1.6 bar with falling downstream flow latches a SUSPECTED_BREACH and auto-isolates the affected branch. Both criticals require manual reset. Hysteresis: a WARN clears only after pressure returns inside 2.1–2.9 bar and holds for 2 minutes, preventing chatter at the band edges.

Recent Trend

Loop manifold pressure in bar, last 14 thirty-second samples:

HLP · 14-sample trend, bar (current 2.5)

Interpretation Guidance

HLP BandReadingLikely DriverAction
< 1.6 barCRIT lowLine breach or pump lossAuto-isolate branch; invoke breach SOP.
1.6–1.99 barWARN lowDemand spike or partial clogRaise pump duty; check emitter flow.
2.2–2.8 barNominalBalanced loopNone; normal operating band.
3.21–3.6 barWARN highPump runaway or downstream valve closedTrim pump duty; verify valve states.
> 3.6 barCRIT highControl failure / blockageVFD to minimum; open relief bypass; isolate.

Related SOPs